ADVANCED AUTOMATION TECHNOLOGIES

Product Catalog

1-6 Model

One of the most widespread design of temperature probes for common industrial usage. It applies to measure temperature of liquid, gas-like and air environments. It may go with a free hex fitting in a kit. The 4-20 mA or RS485 transducer (T-bus/ModBus protocol) can be ordered separately in Z67 enclosure with a cable gland and connect it to the probe cable.

The silicone heat shrink tube is used to avoid kinking a cable, when it's up to 250°С. And the protective spring is used, when it's over 250°С.

1-6 model can be apply as an explosion-proof temperature probe (explosion proof type - intrinsically safe electrical circuit "i"). It provides with the RE shielded cable only.

Note: Manufacturing the 1-6 model with 3 mm diameter is only possible with Cu100 and length up to 30 mm.

Technical specifications

Type and Nominal Resistance Cu50 (ex-USSR), Cu100 (ex-USSR)
Pt50 (ex-USSR), Pt100 (ex-USSR), Pt1000
10kNTC
DS18B20
Type К
Type L (ex- USSR)
Type J
Number of sensors 1, 2
Accuracy Class В (Cu50, Cu100)
Classes АА, А, В (Pt50, Pt100, Pt1000)
1% (10kNTC)
0,5°C (DS18B20)
1, 2 (K, J)
2 (L) 
RTD wire connection 2, 3, 4 wired
2 wired with 2 sensors
2 wired with 3 sensors
Junction type of thermocouples Grounded, ungrounded,
dual ungrounded
Sheath material AISI 321
Process temperature range, °С -50...150 (Cu50, Cu100)
-100...250, -40...100, -50....250, -50...350 (Pt50, Pt100, Pt1000)
-40...120, -20...200 (10kNTC)
-30...100 (DS18B20)
-40...250, -40...400 (type K, J, L)
Thermal inertia, sec 10...15 (RTD)
10...20 (thermocouples)
Pressure, MPa 0,4

Explosion-proof design

Cable type RE
Explosion-proof labelling 0ExiallCT6...T1 X (allowed zones: 0, 1, 2, 20, 21, 22)

Dimensions

Length of the immersion part, L, mm 20, 32, 40, 60, 80, 100, 120, 160, 200, 250, 320, 400, 500
Diameter of the immersion part, mm Ø3, Ø4, Ø5, Ø6

* - distance between the bearing area and the industrial head

 

Application Form to order the product
Data Sheet