2-16 Model
Y-Case Humidity and Temperature Tranducer RS485 uses RS485 interface to transfer data. This wired interface allows to connect consistently up to 30 probes using a single cable line. The transducer is connected to RS485 by 5 wired scheme. For networking it uses FTP 5e cables. RS485 connection is carried out by sealed thread M12 connector with internal terminal block (no soldering). It's able to dismount the transducer easily, when it requires verification or calibration.
Humidity and temperature built-in SHT31 sensor is placed inside of transducer’s case. In addition, it’s available to connect up to two external temperature probes via non-sealed thread M5 connectors. It goes with magnets and mounting boards with screws to mount it easily on the vertical surface.
Technical specifications of transducer
| Number of channels | 2, 4 |
| Available channel configuration | Internal humidity and temperature sensor 1 internal humidity and temperature sensor and 2 external temperature probes |
| Output signal | RS485, T-bus or Modbus RTU Protocols |
| Indication | OLED 0.96’ display |
| Connector | М12FA / M12FD |
| Operating Temperature, °С | -30…60 |
Technical specifications of internal humidity and temperature sensor
| Sensor Curve | SHT31 |
| Process temperature range, °С | -20…60 |
| Process humidity range, % | 0...100 (at temperature 0...60 °C) |
Technical specifications of external temperature probe
| Nominal Resistance | Pt1000 |
| Process temperature range, °С | -196…100, -50…100, -50…250, -50…500 |
| Connector | M5 |
It uses high-contrast OLED display, that shows measurements receiving from all the channels, displays the serial number and RS485 net settings.
СР-06 Junction box

The transducer goes with junction box CP-06 and its power supply. Transducer’s power supply is set up inside of CP-06, as well as the terminal block for easy arrangement of RS485 input and output cables.
Technical specifications of СР-06 junction box
| Input power supply | 12-24 V DC |
| Output power supply | 5 V DC |